RAMSET
RAM 30 UL
Opening
Pressing this button will cause the gate to open.
Stop
Pressing this button will cause the gate to
stop moving.
Closing
Pressing this button will cause the gate to close.
Reset E.R.D. Board
Push all three pushbuttons for approximately
5 seconds. All three L.E.D.’s should blink.
"Intelligate" Control Board
Three pushbuttons are located under the dip switches for operation of the gate (see Figure 11). The opening,
stop
and closing buttons can be utilized to set limit switches and verify proper system operation when
installing or servicing an operator.
PUSHBUTTON CONTROLS
MASTER / SLAVE INSTALLATION
L.E.D.’s light up when Opening,
Closing or Stopped
Figure 11
Figure 10
Set Dip Switch (C8) "Slave Mode" to ON for
slave operator.
(RH) Right Hand operation requires Dip Switch
(C7) "Left/Right" to be ON.
Route low-voltage wires for
Master/Slave in a conduit
separate
from power.
Use 3-stranded, shielded wires
(not supplied) from Master to Slave.
Use jumper
JP7 to JP7
Conduit for Power